AC Load Bank · Power Factor

Resistive-Reactive Load Bank

Resistive and reactive load together, so generators, alternators and paralleling controls are tested the way they really run — at 0.8 power factor and full kVA.

250 – 6,250 kVA0.8 PFkW + kVARParalleling testsCommissioning
6.25 MVA
Max rating
0.8
Power factor
kVAR
Independent
MW
Scale
Same-Day Quotes
Price and lead time today
2-Year Warranty
Backed by our engineering team
North America Made
Built in Toronto, Ontario
Overview

Test the Whole Machine, Not Just the Engine

A resistive test loads the engine but barely asks anything of the alternator and voltage regulator. Real building loads — motors, transformers, drives — draw reactive current too. A resistive-reactive load bank adds controllable inductive load, so the alternator, excitation and paralleling controls are proven at full rated kVA. It is the standard for commissioning critical and paralleled generator plants.

  • Independent kW and kVAR control
  • 0.8 power factor at full rating
  • Proves alternator, regulator and load sharing
  • Transient step-load testing
  • Data logging for commissioning reports
  • Skid or containerized
FIG. 02
Resistive-Reactive Load BankDWGCE-LDB-04-01VIEWPower FactorSCALENTSREV ACANDRON
Resistive-Reactive Load Bank · 250 – 6,250 kVA · 0.8 PF
In Plain Words

Resistive-Reactive Load Bank in plain words

What it does

A load bank that adds inductive (reactive) load to the resistive load, so a generator is tested at the 0.8 power factor it is actually rated for.

Pick it when

  • You must prove the generator at full kVA, not just kW
  • Generators run in parallel and load sharing must be checked
  • Specifications call for 0.8 PF testing

Better choice if…

A simple kW test is enough

See the Portable Resistive →
Features & Upgrades

What's Included

Standard Features
  • Resistive section and reactor section
  • Cooling fans
  • Main breaker
  • Over-temperature, loss-of-airflow, fan-motor overload and control-power-loss protection; element fusing
  • Control panel with full power metering
Optional Upgrades
  • +PC control with automated test sequences
  • +Container housing
  • +Medium-voltage connection
Technical Specifications

Full Specifications

ParameterValue
Rating250 – 6,250 kVA (200 – 5,000 kW + reactive)
Power factor0.8 lagging at full rating; adjustable
Voltage480 – 600 V AC
ControlLocal panel with kW, V, A, Hz readout; optional remote controller and PC software with data logging
ProtectionOver-temperature, loss-of-airflow, fan-motor overload and control-power-loss protection; element fusing
Standards & Compliance

Built to Standard

NFPA 110
Emergency and standby power systems — testing and maintenance
CSA C282
Emergency electrical power supply for buildings — includes periodic load testing
CSA C22.2 No. 14 / UL 508
Industrial control equipment — contactors, controls and wiring
CSA C22.1
Canadian Electrical Code, Part I
Applications

Where It's Used

  • Generator plant commissioning
  • Paralleling switchgear testing
  • Data centres and hospitals
  • Marine and offshore generators
  • Manufacturer test cells
End-to-End Services

From design and specification through factory testing, commissioning, and ongoing maintenance — CANDRON delivers at every phase.

  • Engineering drawings and coordination studies
  • Factory acceptance testing (FAT) with full reports
  • Site commissioning and protection settings
  • Spare parts, training, and maintenance support
FAQ

Common Questions

Generators are rated in kVA at 0.8 power factor. Testing at unity power factor never loads the alternator to its rated current, so problems in the alternator, voltage regulator or load sharing can stay hidden.

Get a Quote

Ready to Spec
Your Project?

Our engineering team responds with specs, lead times, and pricing the same day. Tell us what you need:

  • Generator kVA and voltage
  • Number of generators in parallel
  • Test standard or specification
  • Site access