Single-Phase PolemountDWGCE-LQO-01-ISOVIEW3D ModelSCALENTSREV ACANDRON
Polemount · Overhead Distribution

Single-Phase Polemount Transformer

Overhead transformers for utilities, farms and rural services. Conventional or completely self-protected, with cover-mounted HV and side-mounted LV bushings. 5 – 333 kVA, 120/240 V.

5 – 333 kVAUp to 34.5 kV120/240 VConventional or CSPCSA C2.1
333 kVA
Max rating
34.5 kV
Max primary
CSP
Self-protected opt.
Pole
Mounting
Same-Day Quotes
Price and lead time today
2-Year Warranty
Backed by our engineering team
North America Made
Built in Toronto, Ontario
Overview

The Workhorse of Overhead Lines

Pole-mounted transformers serve most rural and many older urban neighbourhoods. The HV bushing on the cover connects to the overhead line through a fuse cutout; the LV bushings on the side feed the service drops. A conventional unit relies on that external cutout and arrester. A completely self-protected (CSP) unit carries its own internal fuse, surge arrester and secondary breaker — handy where line crews want fewer parts on the pole.

  • Conventional or completely self-protected (CSP)
  • Cover-mounted HV, side-mounted LV bushings
  • Hanger brackets for standard pole mounting
  • Corrosion-resistant finish
  • Mineral oil or FR3 natural ester
  • Utility specifications welcome
FIG. 02
Single-Phase Polemount TransformerDWGCE-LQO-01-GAVIEWElevationSCALENTSREV ACANDRON
Single-Phase Polemount Transformer · 5 – 333 kVA · up to 34.5 kV
In Plain Words

Single-Phase Polemount Transformer in plain words

What it does

The round can on a hydro pole: it takes overhead distribution voltage and steps it down to 120/240 V for homes, farms and small businesses.

Pick it when

  • The distribution line is overhead
  • Loads are single-phase 120/240 V
  • You want a simple, low-cost installation with no pad

Better choice if…

The service is underground

See the Single-Phase Padmount →
Features & Upgrades

What's Included

Standard Features
  • Round, sealed steel tank with bolted cover and cover ground strap
  • Cover-mounted HV bushing(s); side-mounted LV bushings
  • Hanger brackets to IEEE C57.12.20
  • Pressure relief device
  • Arrester mounting pads and grounding provisions
  • Aluminum or copper windings
  • ANSI 70 grey finish
  • Anodized aluminum or stainless nameplate
Optional Upgrades
  • +CSP package: internal weak-link fuse, arrester and secondary breaker
  • +FR3 natural ester fluid
  • +Stainless-steel tank
  • +Internal fault detector
  • +Dual-voltage primary
  • +200 A, 25 kV load-break HV bushing
Technical Specifications

Full Specifications

ParameterValue
Rating5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333 kVA
Primary voltageUp to 34.5 kV GrdY/19.92 kV (e.g. 16 kV, 14.4 kV, 7.97 kV, 4.8 kV)
Secondary voltage120/240 V (240/480 V and 347/600 V on request)
TypeConventional or completely self-protected
CoolingONAN
FluidType II mineral oil, or FR3 natural ester (less-flammable, biodegradable)
Temperature rise65 °C average winding rise
TestsRoutine tests per IEEE C57.12.90 and CSA C2.1: ratio, polarity and phase relation, winding resistance, no-load and load losses, impedance, applied and induced potential, leak test
Standards & Compliance

Built to Standard

CSA C2.1
Single- and three-phase liquid-filled distribution transformers — Canadian requirements
CSA C802.1
Minimum efficiency values for liquid-filled distribution transformers
IEEE C57.12.20
Overhead-type distribution transformers (500 kVA and smaller)
IEEE C57.12.00
General requirements for liquid-immersed distribution, power and regulating transformers
IEEE C57.12.90
Test code for liquid-immersed transformers — how every routine test is run
DOE 10 CFR Part 431
U.S. minimum efficiency for liquid-immersed distribution transformers
Applications

Where It's Used

  • Rural and farm services
  • Residential overhead distribution
  • Small commercial and lighting loads
  • Pumping stations and remote equipment
  • Utility storm replacement stock
End-to-End Services

From design and specification through factory testing, commissioning, and ongoing maintenance — CANDRON delivers at every phase.

  • Engineering drawings and coordination studies
  • Factory acceptance testing (FAT) with full reports
  • Site commissioning and protection settings
  • Spare parts, training, and maintenance support
FAQ

Common Questions

Follow the utility standard. Conventional units rely on an external cutout and arrester on the pole; CSP units have the fuse, arrester and a secondary breaker built in, which protects the transformer from overloads on the service side as well.

Mineral oil is the economical standard. FR3 natural ester is made from vegetable oil: it is biodegradable, has a fire point above 300 °C (a “less-flammable” fluid), and slows paper insulation ageing. Choose it near buildings, water, or anywhere the fire code or environmental permit asks for a less-flammable fluid.

Get a Quote

Ready to Spec
Your Project?

Our engineering team responds with specs, lead times, and pricing the same day. Tell us what you need:

  • kVA rating
  • Primary voltage
  • Secondary voltage
  • Conventional or CSP
  • Utility specification
  • Quantity
Same-Day Response

Send us your project details and we'll respond with a price, lead time, and any clarifying questions — typically within a few hours.

Request a Quote →Or call +1 (647) 616-2595